2.1 The transformers shall be suitable for outdoor/indoor installation with following system particulars and should be suitable for service under fluctuations in supply voltage as permissible under Indian Electricity Act
Transformers shall be suitable for continuous operation with a frequency variation of (50 +/-3%) Hz without exceeding specified temperature rise.
the plinth of transformer if the same is ready at respective site or at suitable location as per direction of site-in-charge of customer. 2. GENERAL REQUIREMENT: The Transformer shall be multi-winding, oil immersed complying as per Specific Technical parameters and suitable for outdoor installation.
transformers (400/33 kV, 220/33 kV & 132/33 kV) at the pooling stations. Hence, there is need for preparation of standard specification of transformer for solar park pooling station as they are most expensive & vital asset and play crucial role in reliable evacuation of …
Transformer GTP - Study on GTP of the equipment's required in ...
The transformer shall be capable of operating in accordance with the loading guidelines of the standard without exceeding the normal daily use of life and without the transformer winding hot spot temperature exceeding 80 C.
- Reviews: 3
NOTE: The transformer make should be approved as per the CEIG / CEA & TSSPDCL norms.
The transformer shall be suitable for outdoor service as step down transformer. The electrical parameters of the transformer shall be as follows: 1 Rated HV voltage
immersed, naturally air cooled Power Transformer with on load tap changer for 10MVA and 6.3MVA transformer as per detail furnished hereafter. 1.02: The transformer offered shall be complete with all parts and accessories which are necessary
The equipment shall be installed on double pole structure or plinth at outdoor location any where in West Bengal in the Distribution system of WBSEDCL to effect power supply to the consumer. 4.00 PRINCIPAL PARAMETERS : 4.01 The transformers shall be suitable for outdoor installation with three phase, 50 Hz, 11 KV system in which
The transformers shall be suitable for outdoor installation with three phase, 50 Hz, 11 kV system in which the neutral is effectively earthed and they should be suitable for service with fluctuations in supply voltage upto plus 12.5% to minus 12.5%. The transformers shall conform to the following specific parameters: